Comparison of several methods for calculating power line electromagnetic interference levels and calibration with long term data

Five different methods for predicting foul-weather electromagnetic interference from power lines have been studied. Differences between the predictions in excess of 10 dB are common. Each method has been optimized by adding a constant chosen to minimize the difference between predictions and a set o...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1992-04, Vol.7 (2), p.903-913
Hauptverfasser: Olsen, R.G., Schennum, S.D., Chartier, V.L.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Five different methods for predicting foul-weather electromagnetic interference from power lines have been studied. Differences between the predictions in excess of 10 dB are common. Each method has been optimized by adding a constant chosen to minimize the difference between predictions and a set of long-term measurements. The rationale for doing this is that each generation function was developed under somewhat different weather conditions. The best optimized method is the one with the smallest difference. The best methods have, respectively, 1.7 and 4.4 db RMS differences between average stable foul and average fair-weather measurements.< >
ISSN:0885-8977
1937-4208
DOI:10.1109/61.127097