A New Distance Protection Scheme Based on Improved Virtual Measured Voltage

Fault resistance causes conventional distance protection to operate incorrectly, threatening the safe operation of power system. The immunity to fault resistance is improved by utilizing fault-point voltage, measured current, and setting impedance to construct the virtual measured voltage. Then, a n...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2020-04, Vol.35 (2), p.774-786
Hauptverfasser: Liang, Yingyu, Li, Wulin, Lu, Zhengjie, Xu, Guanjun, Wang, Cong
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Fault resistance causes conventional distance protection to operate incorrectly, threatening the safe operation of power system. The immunity to fault resistance is improved by utilizing fault-point voltage, measured current, and setting impedance to construct the virtual measured voltage. Then, a new distance protection scheme, known as protection scheme I, is presented to identify in-zone and out-of-zone faults by comparing the amplitudes of the original and virtual measured voltages. Then, the original and virtual measured voltages are improved by a special voltage phasor in phase with the fault-point voltage phasor. Based on the improved original and virtual measured voltages, another distance protection scheme is presented, namely protection scheme II. The two proposed protection schemes are immune to fault resistance and load current and operate well under all types of faults. However, protection scheme II has higher sensitivity to fault detection compared with protection scheme I. Simulation results verify the correctness and effectiveness of the two proposed schemes.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2019.2926295