Impact of DC bias on differential protection of converter transformers
•The impact of DC bias on converter transformer differential protection is thoroughly analyzed.•A simulation model of converter transformer under the effect of DC bias is proposed.•DC bias is divided into ERC-induced and GIC-induced, and they are represented by different signatures.•Relay testing is...
Gespeichert in:
Veröffentlicht in: | International journal of electrical power & energy systems 2020-02, Vol.115, p.105426, Article 105426 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | •The impact of DC bias on converter transformer differential protection is thoroughly analyzed.•A simulation model of converter transformer under the effect of DC bias is proposed.•DC bias is divided into ERC-induced and GIC-induced, and they are represented by different signatures.•Relay testing is conducted to determine the impact of DC bias on converter transformer differential protection.
Converter transformers in high-voltage direct current (HVDC) systems are often subjected to DC bias induced by earth return currents (ERCs) from HVDC systems or by geomagnetically induced currents (GICs). DC bias may adversely affect the performance of converter transformers, but its impact on the protection of converter transformers remains uncertain. This paper thoroughly investigates the response of converter transformer differential protection under the effect of DC bias. The network was simulated in PSCAD/EMTDC, and the modeled components included the converter transformers, the current transformers (CTs), and the DC bias signatures. The fault currents generated by the simulator were downloaded into a numerical relay and its operating behavior was observed. The results indicated the pre-existing harmonics, induced by DC bias, do not cause harmonic blocking to incorrectly inhibit the relay for in-zone faults; and any spurious trip, caused by DC bias, can be prevented by appropriate harmonic blocking and the use of a higher slope 2 in the differential current versus bias current characteristic. It was demonstrated the low-frequency characteristic of GIC did not pose any new threats to differential protection. This indicates the low-frequency characteristic of GIC is negligible when investigating the impact of GIC. |
---|---|
ISSN: | 0142-0615 1879-3517 |
DOI: | 10.1016/j.ijepes.2019.105426 |