Optimization of Serial Combined System of Ground-Coupled Heat Pump and Solar Collector

A mathematical optimization model was set up for a ground-solar combined system based on in-situ experimental results, in which the solar collector was combined serially with a ground-coupled heat pump (GCHP). The universal optimal equations were solved by the constrained variable metric method cons...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Transactions of Tianjin University 2009-02, Vol.15 (1), p.37-42
1. Verfasser: 赵军 陈雁 卢素珍 崔俊奎
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A mathematical optimization model was set up for a ground-solar combined system based on in-situ experimental results, in which the solar collector was combined serially with a ground-coupled heat pump (GCHP). The universal optimal equations were solved by the constrained variable metric method considering both the performance and economics. Then the model was applied to a specific case concerning an actual solar assisted GCHP system for space heating. The results indicated a system coefficient of performance (COP) of 3.9 for the optimal method under the serial heating mode, and 3.2 for the conventional one. In addition, the optimum solution also showed advantages in energy and cost saving, leading to a 16.7% improvement in the heat pump performance at 17.2% less energy consumption and 11.8% lower annual cost, respectively.
ISSN:1006-4982
1995-8196