An Indirect Procedure for Real-Time Monitoring the Neutral Conductor Deterioration in Three-Phase Distribution Networks
[EN] An indirect procedure for real-time monitoring the neutral conductor condition in threephase distribution networks, based on watching over the growth of a novel parameter (Dt), has been described in this paper. The parameter Dt has been defined as the relationship between the neutral-displaceme...
Gespeichert in:
Hauptverfasser: | , , , , |
---|---|
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | [EN] An indirect procedure for real-time monitoring the neutral conductor condition in threephase
distribution networks, based on watching over the growth of a novel parameter (Dt), has
been described in this paper. The parameter Dt has been defined as the relationship between the
neutral-displacement power and Buchholz¿s apparent power measured at the fundamental frequency
in the loads of the distribution networks for any condition of the neutral conductor and in its nominal
conditions. The effectiveness of this procedure has been compared with other traditional indirect
procedures, such as the surveillance of the RMS values of the line-to-neutral load voltages or their
zero-sequence component. The practical application on a real distribution network reveals that the
growth of the parameter Dt in the early stages of the breaking process of the neutral conductor follows
a straight line whose equation is known for each length and section of that conductor, regardless of
the loads and the voltage regulation of the transformer of the distribution network. This characteristic
of the Dt parameter shows that the proposed procedure is suitable for monitoring neutral conductor
deterioration and can be used for preventive maintenance of distribution networks.
This research was funded by the European Commission under the LIFE Program, project
LIFE21-CET-LOCAL-GENERA, grant number 101077073.