Final report on supplementary comparison EURAMET.EM-S29: Traceability of DC high voltage reference measuring systems up to 200 kV
The purpose of the EURAMET supplementary comparison EURAMET.EM-S29 was to compare the calibration and measurement capabilities of the participating institutes. The pilot laboratory was the Laboratorio Central Oficial de Electrotecnia (LCOE, Madrid, Spain), and the other participants were the followi...
Gespeichert in:
Veröffentlicht in: | Metrologia 2012-01, Vol.49 (1A), p.1001-1001 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The purpose of the EURAMET supplementary comparison EURAMET.EM-S29 was to compare the calibration and measurement capabilities of the participating institutes. The pilot laboratory was the Laboratorio Central Oficial de Electrotecnia (LCOE, Madrid, Spain), and the other participants were the following other six EURAMET national metrology institutes: BIM (Bulgaria), MIKES (Finland), PTB (Germany), SP (Sweden), UME (Turkey) and VSL (The Netherlands), and the COOMET national institute VNIIMS (Russia). A 200 kV DC reference measuring system provided by LCOE was used as a travelling reference measuring system (TRMS). The comparison measurements were carried out between November 2007 and April 2010. According to the technical protocol, two different types of measurements had to be made: determination of the assigned scale factor of the TRMS between 1 kV and 200 kV, positive and negative polarity, and short-term stability of the measuring systems used. For each voltage level and polarity, a comparison reference value was calculated. Compatibility of each participant with the corresponding comparison reference values and between any pair of laboratories was also obtained. Results of the comparison offered a good opportunity to check the calibration and measurement capabilities of the participants in the field of high voltage DC measurement. The reported results also demonstrate the importance of taking care in order to cancel the influence of the self-heating of the TRMS. Main text. To reach the main text of this paper, click on Final Report [http://www.bipm.org/utils/common/pdf/final_reports/EM/S29/EURAMET.EM-S29.pdf] . Note that this text is that which appears in Appendix B of the BIPM key comparison database kcdb.bipm.org/ [http://kcdb.bipm.org/] . The final report has been peer-reviewed and approved for publication by EURAMET, according to the provisions of the CIPM Mutual Recognition Arrangement (MRA). |
---|---|
ISSN: | 0026-1394 1681-7575 1681-7575 |
DOI: | 10.1088/0026-1394/49/1A/01001 |