Fire tests with automatic sprinklers in an intermediate scale tunnel

A series of 1:3 intermediate scale tunnel fire tests was performed to investigate the performance of a fully automatic sprinkler system in a road tunnel. The experiments were carried in a container tunnel with scaled geometry, using wood pallets as the fire source to simulate HGV fires. The activati...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Fire safety journal 2022-05, Vol.129, p.103567, Article 103567
Hauptverfasser: Ingason, Haukur, Li, Ying Zhen, Arvidson, Magnus, Jiang, Lei
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A series of 1:3 intermediate scale tunnel fire tests was performed to investigate the performance of a fully automatic sprinkler system in a road tunnel. The experiments were carried in a container tunnel with scaled geometry, using wood pallets as the fire source to simulate HGV fires. The activation of the sprinklers was simulated by using thermocouples that corresponded to a given Thermal Response Index (RTI) of a sprinkler bulb or a link. A total of 12 tests were carried out with varying longitudinal velocities (0.8–1.7 m/s), sprinkler activation temperatures (68–141 °C), water densities (2.9–8.7 mm/min) and types of arrangement of the fuel. The activation times, number of activated sprinklers, maximum heat release rates and other key parameters are presented and analyzed. The results show that the water density plays a key role in the performance of the automatic sprinkler systems tested. A high tunnel ventilation velocity, low water density and low sprinkler activation temperature are not recommended. •A series of intermediate scale tunnel fire tests was performed.•Performance of a fully automatic sprinkler system was investigated.•Varying velocities, activation temperatures and water densities were considered.•Important results including heat release rates are presented and analyzed.
ISSN:0379-7112
1873-7226
1873-7226