Active and reactive power control of a VSC-HVdc
Voltage source converter-based HVdc (VSC-HVdc) systems have the ability to rapidly control the transmitted active power, and also to independently exchange reactive power with transmissions systems. Due to these characteristics, VSC-HVdcs with a suitable control scheme can offer an alternative means...
Gespeichert in:
Veröffentlicht in: | Electric power systems research 2008-10, Vol.78 (10), p.1756-1763 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Voltage source converter-based HVdc (VSC-HVdc) systems have the ability to rapidly control the transmitted active power, and also to independently exchange reactive power with transmissions systems. Due to these characteristics, VSC-HVdcs with a suitable control scheme can offer an alternative means to enhance transient stability, to improve power oscillations damping, and to provide voltage support. In this paper, a VSC-HVdc is represented by a simple model, referred to as the injection model. Based on this model, an energy function is developed for a multi-machine power system including VSC-HVdcs. Furthermore, based on Lyapunov theory (control Lyapunov function) and small signal analysis (modal analysis), various control strategies for transient stability and damping of low-frequency power oscillations are derived. |
---|---|
ISSN: | 0378-7796 1873-2046 1873-2046 |
DOI: | 10.1016/j.epsr.2008.03.003 |