Outbreak of Legionnaires' disease in Glasgow Royal Infirmary: microbiological aspects
The bacteriological investigation of an outbreak of Legionnaires' disease in Glasgow Royal Infirmary affecting 16 patients is described. Most of the patients had been treated in high-dependency areas on two floors of the hospital supplied by the same two air-conditioned ventilation systems. The...
Gespeichert in:
Veröffentlicht in: | The Journal of hygiene 1986-12, Vol.97 (3), p.393-403 |
---|---|
Hauptverfasser: | , , , , , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The bacteriological investigation of an outbreak of Legionnaires' disease in Glasgow Royal Infirmary affecting 16 patients is described. Most of the patients had been treated in high-dependency areas on two floors of the hospital supplied by the same two air-conditioned ventilation systems. The source of infection was traced to contamination of a cooling tower from which a plume of spray discharged into the intake vents of the two ventilation systems. Rubber grommets within the cooling tower probably provided a nidus of infection there. The control and management of the outbreak are discussed: a policy of frankness about the course and progress of the investigations was adopted and helped to allay anxiety on the part of both staff and media. |
---|---|
ISSN: | 0022-1724 2396-8184 |
DOI: | 10.1017/S0022172400063580 |