Design Criteria for Primary/Secondary and Primary-Loop-Only Systems

If the installed number of chillers in the plant (Ni) is less than Nreq, then WFTDR sub(REQ) is greater than WFTDR sub(AVLP/S PLOVF) and the application of the P/S system will be beneficial from the energy-conservation point of view as compared with a PLOVF system. If Ni is greater than or equal to...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Heating/Piping/Air Conditioning Engineering : HPAC 2011-10, Vol.83 (10), p.42-49
Hauptverfasser: Burd, AlexanderL, Burd, GalinaS
Format: Magazinearticle
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:If the installed number of chillers in the plant (Ni) is less than Nreq, then WFTDR sub(REQ) is greater than WFTDR sub(AVLP/S PLOVF) and the application of the P/S system will be beneficial from the energy-conservation point of view as compared with a PLOVF system. If Ni is greater than or equal to N sub(REQ), then WFTDR sub(REQ) is less than or equal to WFTDR sub(AVLP/S PLOVF), and both P/S and PLOVF systems are equally energy-efficient.