Design Criteria for Primary/Secondary and Primary-Loop-Only Systems
If the installed number of chillers in the plant (Ni) is less than Nreq, then WFTDR sub(REQ) is greater than WFTDR sub(AVLP/S PLOVF) and the application of the P/S system will be beneficial from the energy-conservation point of view as compared with a PLOVF system. If Ni is greater than or equal to...
Gespeichert in:
Veröffentlicht in: | Heating/Piping/Air Conditioning Engineering : HPAC 2011-10, Vol.83 (10), p.42-49 |
---|---|
Hauptverfasser: | , |
Format: | Magazinearticle |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | If the installed number of chillers in the plant (Ni) is less than Nreq, then WFTDR sub(REQ) is greater than WFTDR sub(AVLP/S PLOVF) and the application of the P/S system will be beneficial from the energy-conservation point of view as compared with a PLOVF system. If Ni is greater than or equal to N sub(REQ), then WFTDR sub(REQ) is less than or equal to WFTDR sub(AVLP/S PLOVF), and both P/S and PLOVF systems are equally energy-efficient. |
---|---|