Choosing the Right Makeup-Air Unit

The direct-fired units have no heat exchanger and no flue. The burner is mounted directly in the conditioned-air stream (Figure 1). These units are designed to provide virtually complete combustion. Most promotional literature lists 100-percent combustion efficiency but, realistically, you can count...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Heating/Piping/Air Conditioning Engineering : HPAC 2004-11, Vol.76 (11), p.66-68
1. Verfasser: Tinsley, Robert W
Format: Magazinearticle
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The direct-fired units have no heat exchanger and no flue. The burner is mounted directly in the conditioned-air stream (Figure 1). These units are designed to provide virtually complete combustion. Most promotional literature lists 100-percent combustion efficiency but, realistically, you can count on 92- to 96-percent combustion efficiency. Additionally, turndown ratios on direct-fired units are typically 10 times what can be expected on an indirect-fired unit, 25:1 as opposed to 2.5:1.