Optimal thermal operation of liquid-cooled electronic chips
A novel framework is developed to determine the optimal operating conditions of water cooled microprocessor chips through a tradeoff between heat recovery from the coolant and the chip thermal reliability. For illustration, a manifold microchannel heat sink is evaluated experimentally and computatio...
Gespeichert in:
Veröffentlicht in: | International journal of heat and mass transfer 2012-03, Vol.55 (7-8), p.1957-1969 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A novel framework is developed to determine the optimal operating conditions of water cooled microprocessor chips through a tradeoff between heat recovery from the coolant and the chip thermal reliability. For illustration, a manifold microchannel heat sink is evaluated experimentally and computationally. First, a single objective optimization is demonstrated by combining the heat recovery and chip reliability into a single parameter. Then, multi-objective optimizations are performed by using Pareto optimality and Multi-Criteria Design Analysis. Using conservative guidelines, these approaches suggest that for an optimal coolant flow rate of 1l/m, optimal coolant inlet temperature lies between 40 and 50°C. |
---|---|
ISSN: | 0017-9310 1879-2189 |
DOI: | 10.1016/j.ijheatmasstransfer.2011.11.052 |