Dielectric breakdown strength correlation with time-to-failure during wet aging of XLPE-insulated cables
This paper reviews two sets of failure information, the GMTF (a parameter obtained from time-to-failure results) and GMBD stress (a parameter that is calculated from AC breakdown test results), and suggests a correlation. The test results were obtained from accelerated aging experiments on full-size...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 1999-07, Vol.14 (3), p.750-755 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper reviews two sets of failure information, the GMTF (a parameter obtained from time-to-failure results) and GMBD stress (a parameter that is calculated from AC breakdown test results), and suggests a correlation. The test results were obtained from accelerated aging experiments on full-sized medium voltage cables in carefully controlled and monitored water-filled tanks. Results show that the ambient temperature AC breakdown strength for equivalently aged cables is influenced primarily by voltage stress during aging-not by the aging temperature. The AC breakdown strength on equivalently aged cables was also shown to decrease with reductions in the aging voltage at all aging temperatures. |
---|---|