Experimental study on sudden-short-circuit characteristic of synchronous generator with SCFCL

Superconducting fault current limiters (SCFCLs) are expected to improve the reliability of power systems. An SCFCL of a transformer type with adjustable trigger current level was proposed. Three SCFCLs of this type for 3-phase AC power source were designed and made. The trigger current level of each...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on applied superconductivity 2001-03, Vol.11 (1), p.2343-2346
Hauptverfasser: Hatta, B., Nitta, T., Muroya, S., Shirai, Y., Kitagawa, T.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Superconducting fault current limiters (SCFCLs) are expected to improve the reliability of power systems. An SCFCL of a transformer type with adjustable trigger current level was proposed. Three SCFCLs of this type for 3-phase AC power source were designed and made. The trigger current level of each trial SCFCL can be adjusted to equal value, and the SCFCLs can be used as a 3-phase SCFCL. As preliminary tests, sudden-short circuit tests with a 20 kVA synchronous generator are carried out. Limiting tests of the 3-phase SCFCL at fault are carried out with the synchronous generator. The effect of 3-phase SCFCL and the characteristics of the synchronous generator are studied experimentally.
ISSN:1051-8223
1558-2515
DOI:10.1109/77.920331