On the use of singular perturbations to neglect the dynamic saliency of synchronous machines
A common approximation used in the analysis of power systems is the neglect of the dynamic saliency in synchronous machines. In this paper, it is shown that eliminating the error associated with neglecting dynamic saliency can be accomplished with the addition of a singular perturbation(s) into the...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on energy conversion 2002-09, Vol.17 (3), p.385-391 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A common approximation used in the analysis of power systems is the neglect of the dynamic saliency in synchronous machines. In this paper, it is shown that eliminating the error associated with neglecting dynamic saliency can be accomplished with the addition of a singular perturbation(s) into the machine model. By considering the elimination of error in such a way, singular-perturbation-based model-order-reduction techniques are used to derive detailed- and reduced-order models of synchronous machines where dynamic saliency is eliminated with zero error and no added numerical cost. |
---|---|
ISSN: | 0885-8969 1558-0059 |
DOI: | 10.1109/TEC.2002.801988 |