Fault Location for Underground Power Cable Using Distributed Parameter Approach

This paper proposes an extensive fault location model for underground power cable in distribution system using voltage and current measurements at the sending-end. First, an equivalent circuit that models a faulted underground cable system is analyzed using distributed parameter approach. Then, the...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power systems 2008-11, Vol.23 (4), p.1809-1816
Hauptverfasser: Yang, Xia, Choi, Myeon-Song, Lee, Seung-Jae, Ten, Chee-Wooi, Lim, Seong-Il
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper proposes an extensive fault location model for underground power cable in distribution system using voltage and current measurements at the sending-end. First, an equivalent circuit that models a faulted underground cable system is analyzed using distributed parameter approach. Then, the analysis of sequence networks in three-phase network is obtained by applying the boundary conditions. This analysis is used to calculate a fault distance in single section using voltage and current equations. The extension to multi-section is further analyzed based on Korean distribution systems. This method is an iterative process to determine a faulted section from the network. Finally, the case studies are evaluated with variations of fault distance and resistance, which also includes the evaluation of its robustness to load uncertainty.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.2008.2002289