Analytical calculation and stochastic assessment of voltage sags

In this paper, analytical expressions for the calculation of voltage sag magnitude due to faults at every point of a meshed or radial power network are derived. Balanced and unbalanced faults are considered and the effect of power transformers is taken into account. The following methods for stochas...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2006-07, Vol.21 (3), p.1727-1734
Hauptverfasser: Moschakis, M.N., Hatziargyriou, N.D.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this paper, analytical expressions for the calculation of voltage sag magnitude due to faults at every point of a meshed or radial power network are derived. Balanced and unbalanced faults are considered and the effect of power transformers is taken into account. The following methods for stochastic assessment of voltage sag magnitude are compared using these expressions: the method of critical distances, method of fault positions, and Monte Carlo method. The minimum required number of fault positions and iterations assumed by the two methods in order to achieve results of acceptable accuracy are determined.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2006.874108