A New Strategy for Determining Fault Zones in Distance Relays

A new strategy (denoted P-SS) for estimating the correct fault zone in distance relays is introduced. The main difference between the P-SS and conventional setting strategies is that the P-SS does not depend on fixed boundaries for backup zones. It depends on exchanging information between local rel...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2008-10, Vol.23 (4), p.1857-1863
Hauptverfasser: Gilany, M., Al-Kandari, A., Madouh, J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A new strategy (denoted P-SS) for estimating the correct fault zone in distance relays is introduced. The main difference between the P-SS and conventional setting strategies is that the P-SS does not depend on fixed boundaries for backup zones. It depends on exchanging information between local relays in the same station in addition to a command from the remote end relay. With the proposed strategy, zone-1 covers the entire length of the protected line, zone-2 covers the entire length of any next line irrespective of its length, and zone-3 covers the entire length of any line next to zone-2. The governing rules for the proposed strategy are presented. The strategy is examined against a wide range of setting problems of a real part of a high-voltage network with real relay settings. The results confirm that the P-SS achieves the required accurate, sensitive, and selective relay operation.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2008.2002871