Acceptability of Four Transformer Top-Oil Thermal ModelsaPart II: Comparing Metrics

The acceptability of four transformer top-oil thermal models is examined vis-a-vis training with measured data. Acceptability is defined as having the qualities of adequacy, consistency, and accuracy. Metrics are used to characterize the likely deficiencies of these models. It is shown that the clas...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2008-01, Vol.23 (2)
Hauptverfasser: Jauregui-Rivera, L, Tylavsky, D J
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The acceptability of four transformer top-oil thermal models is examined vis-a-vis training with measured data. Acceptability is defined as having the qualities of adequacy, consistency, and accuracy. Metrics are used to characterize the likely deficiencies of these models. It is shown that the classical IEEE/ANSI standard model is unacceptable for model identification purposes. The linear top-oil model is acceptable for FOFA transformers but not NOFA. The models by Susa et al. [7] and Swift et al. [5], [6], may be useful for FOFA transformers and NOFA transformers. Further research with larger training data sets is warranted.
ISSN:0885-8977
DOI:10.1109/TPWRD.2007.905576