Energy saving in HVAC systems using nanofluid

The present study tries to use the methanol-silver nanofluid filled thermosyphon heat exchanger and compares the effectiveness as well as energy saving with pure methanol. Experimental results show that using methanol-silver nanofluid, leads to energy saving around 8.8–31.5% for cooling and 18–100%...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 2011-06, Vol.31 (8), p.1543-1545
Hauptverfasser: Firouzfar, Ehsan, Soltanieh, Mohammad, Noie, S. Hossien, Saidi, S. Hassan
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The present study tries to use the methanol-silver nanofluid filled thermosyphon heat exchanger and compares the effectiveness as well as energy saving with pure methanol. Experimental results show that using methanol-silver nanofluid, leads to energy saving around 8.8–31.5% for cooling and 18–100% for reheating the supply air stream in an air conditioning system. ► This study tries to use the silver-nanofluid filled thermosyphon heat exchanger. ► Experimental data on the effectiveness and energy saving with nanofluid is presented. ► The effect of temperature and humidity on the effectiveness has been investigated. ► Ag-nanofluid, leads to energy saving 8.8–31.5% for cooling and 18–100% for reheating. ► The nanofluid will enhance the thermal conductivity of thermosyphon heat exchanger.
ISSN:1359-4311
DOI:10.1016/j.applthermaleng.2011.01.029