Energy saving in HVAC systems using nanofluid
The present study tries to use the methanol-silver nanofluid filled thermosyphon heat exchanger and compares the effectiveness as well as energy saving with pure methanol. Experimental results show that using methanol-silver nanofluid, leads to energy saving around 8.8–31.5% for cooling and 18–100%...
Gespeichert in:
Veröffentlicht in: | Applied thermal engineering 2011-06, Vol.31 (8), p.1543-1545 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The present study tries to use the methanol-silver nanofluid filled thermosyphon heat exchanger and compares the effectiveness as well as energy saving with pure methanol. Experimental results show that using methanol-silver nanofluid, leads to energy saving around 8.8–31.5% for cooling and 18–100% for reheating the supply air stream in an air conditioning system.
► This study tries to use the silver-nanofluid filled thermosyphon heat exchanger. ► Experimental data on the effectiveness and energy saving with nanofluid is presented. ► The effect of temperature and humidity on the effectiveness has been investigated. ► Ag-nanofluid, leads to energy saving 8.8–31.5% for cooling and 18–100% for reheating. ► The nanofluid will enhance the thermal conductivity of thermosyphon heat exchanger. |
---|---|
ISSN: | 1359-4311 |
DOI: | 10.1016/j.applthermaleng.2011.01.029 |