Controlled Evaluation of Copper-Silver Ionization in Eradicating Legionella pneumophila from a Hospital Water Distribution System

A controlled evaluation was made of the efficacy of copper-silver ionization in eradicating Legionella pneumophila from a hospital water supply, Copper-silver ionization units were installed on the hot water recirculation line of one building with water fixtures positive for Legionella species. Anot...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:The Journal of infectious diseases 1994-04, Vol.169 (4), p.919-922
Hauptverfasser: Liu, Zeming, Stout, Janet E., Tedesco, Lou, Boldin, Marcie, Hwang, Charles, Diven, Warren F., Yu, Victor L.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A controlled evaluation was made of the efficacy of copper-silver ionization in eradicating Legionella pneumophila from a hospital water supply, Copper-silver ionization units were installed on the hot water recirculation line of one building with water fixtures positive for Legionella species. Another building with the same water supply served as a control. Legionella species persisted within the system when copper and silver concentrations were