Periodic high-temperature heat pumps for industrial heat recovery—Part II. Example of application and design of apparatus
Using a drying process as an example, the use of a periodic high-temperature heat pump for industrial heat recovery is investigated. The investigation shows that by using a special control system and two buffer reservoirs, the thermal powers of adsorber, evaporator and condenser can be kept constant...
Gespeichert in:
Veröffentlicht in: | Heat recovery systems & CHP 1992, Vol.12 (3), p.257-269 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Using a drying process as an example, the use of a periodic high-temperature heat pump for industrial heat recovery is investigated. The investigation shows that by using a special control system and two buffer reservoirs, the thermal powers of adsorber, evaporator and condenser can be kept constant in time. The unit under investigation achieves a calculated power density of 6.8 kW/m
3 at an effective capacity of 150 kW. A working cycle lasts 3.5 h and the heat ratio is 1.54. The technical design of an experimental unit in tower configuration is described in detail. |
---|---|
ISSN: | 0890-4332 1878-6898 |
DOI: | 10.1016/0890-4332(92)90054-L |