Periodic high-temperature heat pumps for industrial heat recovery—Part II. Example of application and design of apparatus

Using a drying process as an example, the use of a periodic high-temperature heat pump for industrial heat recovery is investigated. The investigation shows that by using a special control system and two buffer reservoirs, the thermal powers of adsorber, evaporator and condenser can be kept constant...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Heat recovery systems & CHP 1992, Vol.12 (3), p.257-269
Hauptverfasser: Föllinger, T., Merker, G.P.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Using a drying process as an example, the use of a periodic high-temperature heat pump for industrial heat recovery is investigated. The investigation shows that by using a special control system and two buffer reservoirs, the thermal powers of adsorber, evaporator and condenser can be kept constant in time. The unit under investigation achieves a calculated power density of 6.8 kW/m 3 at an effective capacity of 150 kW. A working cycle lasts 3.5 h and the heat ratio is 1.54. The technical design of an experimental unit in tower configuration is described in detail.
ISSN:0890-4332
1878-6898
DOI:10.1016/0890-4332(92)90054-L