The Skip-resistant Sprinkler Concept -- An Experimental Evaluation
A sprinkler with a shield designed to mitigate drop impingement from nearby operating sprinklers is shown experimentally to reduce skipping as compared to the same sprinkler without a shield. As described in a companion article, a model for the response time of a shielded sprinkler has been develope...
Gespeichert in:
Veröffentlicht in: | Journal of fire protection engineering 2009-11, Vol.19 (4), p.291-308 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A sprinkler with a shield designed to mitigate drop impingement from nearby operating sprinklers is shown experimentally to reduce skipping as compared to the same sprinkler without a shield. As described in a companion article, a model for the response time of a shielded sprinkler has been developed and validated with a Plunge Tunnel apparatus. In this article, results from intermediate-scale spray fire tests employing Froude modeling principles with a 1 : 3 scale ratio are used to evaluate sprinkler performance both with and without the shield. By comparing the operation times of adjacent shielded and unshielded sprinklers, the intermediate-scale tests can identify test arrangements where the shielded sprinkler operates while the unshielded sprinkler does not operate. The identified arrangements are then used in a full-scale environment where a series of pan fire tests serve as a proof-of-concept that proper shielding of a sprinkler can reduce skipping in terms of both the sprinkler operation pattern and total number of sprinkler operations. This study successfully demonstrates that proper shielding of a sprinkler can significantly reduce skipping. |
---|---|
ISSN: | 1042-3915 |
DOI: | 10.1177/1042391509346238 |