Experimental investigation on a one-rotor two-stage rotary desiccant cooling system

A one-rotor two-stage rotary desiccant cooling system (OTSDC), in which two-stage dehumidification process is realized by one desiccant wheel, was investigated experimentally. The system was proposed to reduce the volume of two-stage rotary desiccant cooling system (TSDC) with two desiccant wheels w...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Energy (Oxford) 2008-12, Vol.33 (12), p.1807-1815
Hauptverfasser: Ge, T.S., Dai, Y.J., Wang, R.Z., Li, Y.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A one-rotor two-stage rotary desiccant cooling system (OTSDC), in which two-stage dehumidification process is realized by one desiccant wheel, was investigated experimentally. The system was proposed to reduce the volume of two-stage rotary desiccant cooling system (TSDC) with two desiccant wheels without reduction in system performance by using the novel configuration. An experimental setup was designed and built to evaluate the system performance under various operation conditions. The effects of different wheel thicknesses at various rotation speeds under Air-conditioning and Refrigeration Institute (ARI) summer and humid conditions were investigated. It is observed that there exits an optimal rotation speed where moisture removal of the system D and thermal coefficient of performance COP th are both optimal. Moreover, the unit with wheel thickness of 100 mm performs better for its bigger moisture removal D and higher COP th . Generally speaking, the COP th of this unit is around 1.0 when the regeneration temperature is lower than 80 °C. Compared to TSDC, the OTSDC not only preserves the merits of low regeneration temperature and high COP th , but also has a reduced size by about half.
ISSN:0360-5442
DOI:10.1016/j.energy.2008.08.006