Active and reactive power sharing and frequency restoration in a distributed power system consisting of two UPS units

A distributed power system consisting of two uninterrupted power supplies (UPS) is investigated in this paper. Parallel operation of the two sources increases the established power rating of the system. One of the sources can supply the system even when the other system is disconnected due to some f...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:International journal of electrical power & energy systems 2009-06, Vol.31 (5), p.220-226
Hauptverfasser: Parlak, Koray Şener, Özdemir, Mehmet, Aydemir, M. Timur
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A distributed power system consisting of two uninterrupted power supplies (UPS) is investigated in this paper. Parallel operation of the two sources increases the established power rating of the system. One of the sources can supply the system even when the other system is disconnected due to some faults, and this is an important feature. The control algorithm makes sure that the total load is shared between the supplies in accordance with their rated power levels, and the frequency of the supplies are restored to the rated values after the transitions. As the UPSs operate at an optimum power level, losses and faults due to overloading are prevented. The units safely operate without any means of communication between each other. The focus of the work is on the inverter stages of the UPSs. Simulations performed in Matlab Simulink environment have been verified with experimental work via DS1103 controller card.
ISSN:0142-0615
1879-3517
DOI:10.1016/j.ijepes.2009.01.006