UV disinfection of wastewater coagulated with ferric chloride: Recalcitrance and fouling problems

Collimated beam and pilot tests using low pressure or medium pressure UV lamps were conducted to assess the disinfection performance of a municipal wastewater which had been pretreated by ferric chloride coagulation followed by sedimentation. The feed to the UV systems contained high levels of Fe (o...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Water science and technology 1998, Vol.38 (3), p.15-23
Hauptverfasser: Gehr, R., Wright, H.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Collimated beam and pilot tests using low pressure or medium pressure UV lamps were conducted to assess the disinfection performance of a municipal wastewater which had been pretreated by ferric chloride coagulation followed by sedimentation. The feed to the UV systems contained high levels of Fe (often above 3 mg/l); suspended solids and UV254 transmission values were also not ideal (mean approximately 30 mg/l and 32% respectively). The collimated beam tests indicated that the target level of 2,500 coliform forming units/100 ml often could not be reached, and the pilot tests revealed significant fouling after only a few hours. Thus physicochemical effluents of this nature likely require upstream filtration (or a relaxation of the target level) and a continual, automated cleaning system to ensure that performance levels can be maintained.
ISSN:0273-1223
1996-9732
DOI:10.1016/S0273-1223(98)00447-8