On the selection of acoustic/vibration sensors for leak detection in plastic water pipes
Leaks from buried water distribution pipes are commonly located by applying the correlation technique to two measured acoustic/vibration signals on either side of a leak. The effectiveness of the correlation technique for locating leaks in plastic pipes depends on the type of sensors used and their...
Gespeichert in:
Veröffentlicht in: | Journal of sound and vibration 2005-05, Vol.283 (3), p.927-941 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Leaks from buried water distribution pipes are commonly located by applying the correlation technique to two measured acoustic/vibration signals on either side of a leak. The effectiveness of the correlation technique for locating leaks in plastic pipes depends on the type of sensors used and their sensitivities. Based on an analytical model of the cross-correlation of pressure responses established in an earlier study, this paper investigates the behaviour of the cross-correlation coefficient for leak signals measured using pressure, velocity and acceleration sensors. Theoretical predictions show that a measure of pressure responses using hydrophones is effective for measurements where there is a small signal-to-noise ratio (SNR), but a sharper peak correlation coefficient can be achieved if accelerometers are used. The theoretical work is validated to some extent with test data from actual water pipes on a test site in Canada. |
---|---|
ISSN: | 0022-460X 1095-8568 |
DOI: | 10.1016/j.jsv.2004.05.004 |