Transients during 138-kV SF6 breaker switching of low inductive currents
The authors discusses the effects of switching low inductive currents with 138 kV SF/sub 6/ breakers in a petrochemical plant. Switching transients are believed to have contributed to the failure of a 13.8 kV PT and a 13.8 kV air magnetic circuit breaker. The high-frequency transient surge can trans...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on industry applications 1993-07, Vol.29 (4), p.721-727 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The authors discusses the effects of switching low inductive currents with 138 kV SF/sub 6/ breakers in a petrochemical plant. Switching transients are believed to have contributed to the failure of a 13.8 kV PT and a 13.8 kV air magnetic circuit breaker. The high-frequency transient surge can transfer across a transformer due to transformer capacitances between the high- and low-voltage windings. The electromagnetic transient program system (ETPS) model and different case studies are discussed with the effect of different transformer winding capacitances. The interruption mechanism of low inductive currents is also described. This analysis demonstrates the need to conduct switching transient studies and the need for surge arresters on transformer secondary terminals under certain system conditions.< > |
---|---|