105 deg C/140 deg C rated EPR insulated power cables

The excellent long-term operation and field performance of existing EPR cables under the current industry operating temperatures of 90 deg C normal and 130 deg C overload is well known. This paper describes a study for the implementation of a higher temperature rated EPR cable system including acces...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 1996-01, Vol.11 (1), p.31-42
Hauptverfasser: Cinquemani, P L, Kuchta, F L, Rahman, M M, Ruffinazzi, F, Zaopo, A
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The excellent long-term operation and field performance of existing EPR cables under the current industry operating temperatures of 90 deg C normal and 130 deg C overload is well known. This paper describes a study for the implementation of a higher temperature rated EPR cable system including accessories up to a range of 105 deg C continuous service and 140 deg C emergency operation. The investigation has been carried out into the electrical, mechanical, and thermal behavior of the system as a function of temperature. Compatibility has been studied under higher temperature in relation to conductor filling compound and the semi-conducting stress control layer. The results indicate that insulation degradation does not occur under accelerated and elevated temperature testing, concluding that properly formulated and selected materials are both compatible and suitable for the higher temperature ratings
ISSN:0885-8977
DOI:10.1109/61.483998