Voltage correction power flow
A method for power flow solution of weakly meshed distribution and transmission networks is presented. It is based on oriented ordering of network elements. That allows an efficient construction of the loop impedance matrix and rational organization of the processes such as: power summation (backwar...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 1994-04, Vol.9 (2), p.1056-1062 |
---|---|
Hauptverfasser: | , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A method for power flow solution of weakly meshed distribution and transmission networks is presented. It is based on oriented ordering of network elements. That allows an efficient construction of the loop impedance matrix and rational organization of the processes such as: power summation (backward sweep), current summation (backward sweep) and node voltage calculation (forward sweep). The first step of the algorithm is calculation of node voltages on the radial part of the network. The second step is calculation of the breakpoint currents. Then, the procedure continues with the first step, which is preceded by voltage correction. It is illustrated that by using the voltage correction approach, the iterative process of weakly meshed network voltage calculation is faster and more reliable.< > |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.296308 |