Test results for transient excitation boosting at Grand Coulee

Transient excitation boosting (TEB) hardware is discussed, and its design and installation are described. The test results from the hardware commissioning on each generator type are addressed. The results show that an 8% boost in terminal voltage results in about a 50% change in reactive power loadi...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on energy conversion 1991-09, Vol.6 (3), p.367-372
1. Verfasser: Lennon, C.A.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Transient excitation boosting (TEB) hardware is discussed, and its design and installation are described. The test results from the hardware commissioning on each generator type are addressed. The results show that an 8% boost in terminal voltage results in about a 50% change in reactive power loading and about a 10% change in real power with the classical high-frequency damped oscillations which are typical of a step response.< >