Recirculating Flow in Oscillatory U-Tubes
Wastewater treatment facilities often experience undesirable oscillations in water surface elevations due to the potential of unsteady outlet flow. Self-induced oscillations, particularly those generated by the geometry and flow conditions of treatment facilities with a U-tube component, are of part...
Gespeichert in:
Veröffentlicht in: | Journal of hydraulic engineering (New York, N.Y.) N.Y.), 2005-05, Vol.131 (5), p.397-403 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Wastewater treatment facilities often experience undesirable oscillations in water surface elevations due to the potential of unsteady outlet flow. Self-induced oscillations, particularly those generated by the geometry and flow conditions of treatment facilities with a U-tube component, are of particular interest. This study focuses on the U-tube component of an existing wastewater treatment facility where oscillations of constant amplitude and period were observed shortly after the facility was operational. It is assumed that an oscillating U-tube manometer represents this problem, and a numerical model was developed to predict the amplitude and period of the oscillations using Newton’s second law of motion and momentum analysis. A 1-to-4.88-scale physical model of the existing facility was constructed and tested. Numerical model results show good agreement with measured oscillatory characteristics of the existing facility and the physical model. |
---|---|
ISSN: | 0733-9429 1943-7900 |
DOI: | 10.1061/(ASCE)0733-9429(2005)131:5(397) |