A new control method preventing transformer DC magnetization for voltage source self-commutated converters
A DC component contained in an output of a voltage source self-commutated converter causes a converter transformer to be DC-magnetized, in the worst case causing an overcurrent due to saturation. We experienced the DC-magnetization of the converter transformer of a 50 MVA self-commutated SVC install...
Gespeichert in:
Veröffentlicht in: | IEEE Transactions on Power Delivery 1996-07, Vol.11 (3), p.1522-1528 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | A DC component contained in an output of a voltage source self-commutated converter causes a converter transformer to be DC-magnetized, in the worst case causing an overcurrent due to saturation. We experienced the DC-magnetization of the converter transformer of a 50 MVA self-commutated SVC installed in the Shinshinano Substation of Tokyo Electric Power Company when system disturbances occurred by energizing of an adjacent large capacity transformer. After analysing the problem, a novel DC magnetization prevention control was developed that makes a fast flux correction according to the voltage DC component detected in the converter output. This method was applied to the 50 MVA self-commutated SVC and produced satisfactory operation results. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.517512 |