Influence of inductive coupling between leads on ground impedance measurements using the fall-of-potential method

Ground impedance measurements in various soil structures using the fall-of-potential method are modeled, taking into account the inductive coupling between current and potential leads. The variation of the inductive coupling with the separation distance between the current and potential leads, opera...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2001-10, Vol.16 (4), p.739-743
Hauptverfasser: Ma, J., Dawalibi, F.P.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Ground impedance measurements in various soil structures using the fall-of-potential method are modeled, taking into account the inductive coupling between current and potential leads. The variation of the inductive coupling with the separation distance between the current and potential leads, operating frequency, and grounding grid size, is analyzed for uniform and multilayer soils. Numerical results are presented and compared. The analysis quantifies the inductive coupling between current and potential leads for typical separation distances between the leads. Coupling levels presented in this paper can be used as a reference to estimate possible errors in ground impedance measurements.
ISSN:0885-8977
1937-4208
DOI:10.1109/61.956764