A more efficient formulation for computation of the maximum loading points in electric power systems
This paper presents a more efficient formulation for computation of the maximum loading points of power systems. A distinguishing feature of the new formulation is that it is of dimension (n+1), instead of the existing formulation of dimension (2n+1), for n-dimensional load flow equations. This feat...
Gespeichert in:
Veröffentlicht in: | IEEE Transactions on Power Systems 1995-05, Vol.10 (2), p.635-646 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents a more efficient formulation for computation of the maximum loading points of power systems. A distinguishing feature of the new formulation is that it is of dimension (n+1), instead of the existing formulation of dimension (2n+1), for n-dimensional load flow equations. This feature makes computation of the maximum loading points very inexpensive in comparison with those required in the existing formulation. A theoretical basis for the new formulation is provided. The new problem formulation is derived by using a simple reparameterization scheme and exploiting the special properties of the power flow model. Moreover, the proposed test function is shown to be monotonic in the vicinity of a maximum loading point. Therefore, it allows one to monitor the approach to maximum loading points during the solution search process. Simulation results on a 234-bus power system are presented.< > |
---|---|
ISSN: | 0885-8950 1558-0679 |
DOI: | 10.1109/59.387898 |