A more efficient formulation for computation of the maximum loading points in electric power systems

This paper presents a more efficient formulation for computation of the maximum loading points of power systems. A distinguishing feature of the new formulation is that it is of dimension (n+1), instead of the existing formulation of dimension (2n+1), for n-dimensional load flow equations. This feat...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE Transactions on Power Systems 1995-05, Vol.10 (2), p.635-646
Hauptverfasser: Hsiao-Dong Chiang, Jean-Jumeau, R.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents a more efficient formulation for computation of the maximum loading points of power systems. A distinguishing feature of the new formulation is that it is of dimension (n+1), instead of the existing formulation of dimension (2n+1), for n-dimensional load flow equations. This feature makes computation of the maximum loading points very inexpensive in comparison with those required in the existing formulation. A theoretical basis for the new formulation is provided. The new problem formulation is derived by using a simple reparameterization scheme and exploiting the special properties of the power flow model. Moreover, the proposed test function is shown to be monotonic in the vicinity of a maximum loading point. Therefore, it allows one to monitor the approach to maximum loading points during the solution search process. Simulation results on a 234-bus power system are presented.< >
ISSN:0885-8950
1558-0679