A combined directional and faulted phase selector element based on incremental quantities

In this paper, differential incremental or superimposed voltage and current quantities are used in order to determine directionality of a fault in a network. It is shown that this can be accomplished by performing three scalar products between three voltage and current phasor pairs. The relative lev...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2001-10, Vol.16 (4), p.478-484
Hauptverfasser: Benmouyal, G., Mahseredjian, J.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:In this paper, differential incremental or superimposed voltage and current quantities are used in order to determine directionality of a fault in a network. It is shown that this can be accomplished by performing three scalar products between three voltage and current phasor pairs. The relative levels of these same three scalar products can be furthermore used to identify the faulted phases. While, in ultra-high-speed directional comparison relays, superimposed voltage and current had to be treated in the time domain in order to get speed. In this paper, all computations are done in the frequency domain.
ISSN:0885-8977
1937-4208