Compensation strategies for shunt active-filter control

Compensation strategies for control of shunt active filters are compared in the paper. It is shown that the strategy based on unity-power factor control is appropriate when the supply voltage waveform of the plant where the active filter is connected shows significant distortion. As voltage distorti...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power electronics 1994-11, Vol.9 (6), p.587-593
Hauptverfasser: Cavallini, A., Montanari, G.C.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Compensation strategies for control of shunt active filters are compared in the paper. It is shown that the strategy based on unity-power factor control is appropriate when the supply voltage waveform of the plant where the active filter is connected shows significant distortion. As voltage distortion increases, this strategy provides compensated line current having lower harmonic distortion and RMS value with respect to the strategy generally used. This contributes to diminish the current and voltage distortion in networks. The unity-power factor compensation strategy conditions the current flowing in the plant where compensation is realized to fit the voltage waveform, thus reaching a unity power factor. Hence, the line current RMS value is minimum. The comparison of the strategies is performed by both Monte Carlo and ATP simulation.< >
ISSN:0885-8993
1941-0107
DOI:10.1109/63.334773