Effects of heat sinks in metal-oxide surge arresters on ZnO element power dissipation and temperature distribution
The cooling effect of heat sinks placed between the ZnO elements of a surge arrester is evaluated in the context of the IEC Type Test for thermal stability using transient nonlinear finite element analysis with coupled thermal and electric fields to simulate the entire operating duty type test seque...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power delivery 2005-04, Vol.20 (2), p.1402-1408 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The cooling effect of heat sinks placed between the ZnO elements of a surge arrester is evaluated in the context of the IEC Type Test for thermal stability using transient nonlinear finite element analysis with coupled thermal and electric fields to simulate the entire operating duty type test sequence in IEC60099-4. |
---|---|
ISSN: | 0885-8977 1937-4208 |