The setting method of the specific parameters of a superconducting fault current limiter installed at the bus-tie and response of protective relays at operation of the SFCL
We have investigated the setting method of specific parameters for a resistance-type and a rectifier-type superconducting fault current limiter (SFCL) installed in trunk transmission lines and the response of protective relays when SFCLs operate against a system fault. This paper describes the setti...
Gespeichert in:
Veröffentlicht in: | Physica. C, Superconductivity Superconductivity, 2002-08, Vol.372, p.1673-1679 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | We have investigated the setting method of specific parameters for a resistance-type and a rectifier-type superconducting fault current limiter (SFCL) installed in trunk transmission lines and the response of protective relays when SFCLs operate against a system fault. This paper describes the setting method of specific parameters of an SFCL installed at a bus-tie in a trunk substation, response of protective relays such as bus protection and line protection when the SFCL operates against a system fault and countermeasure of preventing tripping a sound line due to unwanted operation of some distance relays resulted by reverse current at operation of the SFCL. |
---|---|
ISSN: | 0921-4534 1873-2143 |
DOI: | 10.1016/S0921-4534(02)01099-7 |