The setting method of the specific parameters of a superconducting fault current limiter installed at the bus-tie and response of protective relays at operation of the SFCL

We have investigated the setting method of specific parameters for a resistance-type and a rectifier-type superconducting fault current limiter (SFCL) installed in trunk transmission lines and the response of protective relays when SFCLs operate against a system fault. This paper describes the setti...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Physica. C, Superconductivity Superconductivity, 2002-08, Vol.372, p.1673-1679
Hauptverfasser: Kameda, Hideyuki, Taniguchi, Haruhito
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:We have investigated the setting method of specific parameters for a resistance-type and a rectifier-type superconducting fault current limiter (SFCL) installed in trunk transmission lines and the response of protective relays when SFCLs operate against a system fault. This paper describes the setting method of specific parameters of an SFCL installed at a bus-tie in a trunk substation, response of protective relays such as bus protection and line protection when the SFCL operates against a system fault and countermeasure of preventing tripping a sound line due to unwanted operation of some distance relays resulted by reverse current at operation of the SFCL.
ISSN:0921-4534
1873-2143
DOI:10.1016/S0921-4534(02)01099-7