Design and implementation of AC voltage dependent current order limiter at Pacific HVDC Intertie

This paper presents design and implementation of AC-voltage dependent current order limiter at the Pacific WDC Intertie. Reactive power and inertial support to the Celilo HVDC terminal have been limited because of new operating requirements for hydropower plants on the lower Columbia River. Under th...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2000-01, Vol.15 (1), p.293-299
Hauptverfasser: Bunch, R., Kosterev, D.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents design and implementation of AC-voltage dependent current order limiter at the Pacific WDC Intertie. Reactive power and inertial support to the Celilo HVDC terminal have been limited because of new operating requirements for hydropower plants on the lower Columbia River. Under these operating conditions, a large set of contingencies was identified when the PDCI can be contributing to AC voltage collapse in the lower Columbia area and to north-south power oscillations. On August 10, 1996, a WSCC system outage occurred under similar generating conditions. To correct the PDCI dynamic response, we designed and implemented the AC-VDCOL function in the PDCI pole controls. The system studies demonstrated consistent benefit of the new controls for the system stability and dynamic performance. The system tests confirmed AC-VDCOL benefit.
ISSN:0885-8977
1937-4208
DOI:10.1109/61.847265