APPLICATION OF OPTIMIZATION TO THE SIZE AND CONTROL SETTINGS OF SHUNT CAPACITORS ON DISTRIBUTION FEEDERS

This paper presents new contributions to the optimization of size and control setting of continuous shunt capacitors on distribution feeders to reduce power and energy losses in the feeders. The current profile is assumed to be a nonlinear function of the distance from the substation, we assume a qu...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Electric machines and power systems 1990-01, Vol.18 (1), p.41-51
Hauptverfasser: SOLIMAN, S. A., EMAM, S. E. A., CHRISTENSEN, G. S.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents new contributions to the optimization of size and control setting of continuous shunt capacitors on distribution feeders to reduce power and energy losses in the feeders. The current profile is assumed to be a nonlinear function of the distance from the substation, we assume a quadratic function for the current profile. As a result, the loss reduction function to be maximized is a highly nonlinear function, we apply the minimum norm theorem in the frame work of functional analysis optimization technique to maximize this function. A set of linear simultaneous equations is obtained. These equations are solved iteratively using the conjugate-gradient methods. We compare our results with that obtained for a uniform current profile that has been done in the literature. Our contributions show a saving in the size of the capacitors and great loss reductions in the feeder.
ISSN:0731-356X
1521-0502