Fire protection of LPG tanks with thin sublimation and intumescent coatings
The results of two full scale fire engulfment tests on a 3.6 m super(3)- LPG tank protected with a sublimation coating (THERMOLAG440) and on a 4.85 m super(3)-LPG tank protected with an intumescent coating (CHARTEK III) are presented. The tests have demonstrated a sufficient vessel safety during 90...
Gespeichert in:
Veröffentlicht in: | Fire technology 1992-01, Vol.28 (3), p.256-269 |
---|---|
1. Verfasser: | |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The results of two full scale fire engulfment tests on a 3.6 m super(3)- LPG tank protected with a sublimation coating (THERMOLAG440) and on a 4.85 m super(3)-LPG tank protected with an intumescent coating (CHARTEK III) are presented. The tests have demonstrated a sufficient vessel safety during 90 minutes of full fire engulfment. Additional furnace tests on CHARTEK III-coated steel plates have been carried out to optimize the necessary coating thickness. |
---|---|
ISSN: | 0015-2684 |