Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study

Although measures to minimize Legionella colonization in sanitary hot water installations are well established, there is little evidence of their long-term effectiveness in hospital buildings. During an 8-year period, hot water in a large hospital building was sampled monthly in areas with suitable...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Water research (Oxford) 2019-02, Vol.149, p.460-466
Hauptverfasser: Gavaldà, Laura, Garcia-Nuñez, Marian, Quero, Sara, Gutierrez-Milla, Carmen, Sabrià, Miquel
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Although measures to minimize Legionella colonization in sanitary hot water installations are well established, there is little evidence of their long-term effectiveness in hospital buildings. During an 8-year period, hot water in a large hospital building was sampled monthly in areas with suitable dimensioning and recirculation and in areas with dead legs and low-use taps. In the former areas, the percentage of Legionella-negative samples was 83.2% when the temperature was ≥55%, 64.9% when between 50.1 °C and 54.0 °C, and 51.6% when ≤50 °C (p for trend