Effectiveness of a neutral electrolysed oxidising water (NEOW) device in reducing Legionella pneumophila in a water distribution system: A comparison between culture, qPCR and PMA-qPCR detection methods

Disinfection of hot water systems is critical for reducing Legionnaires’ disease in high-risk buildings. The use of neutral electrolysed oxidising water (NEOW) is a promising method for the control of microorganisms in hot water systems. However, full-scale evaluations of the efficacy of NEOW device...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Chemosphere (Oxford) 2018-11, Vol.210, p.550-556
Hauptverfasser: Bonetta, Sara, Pignata, Cristina, Bonetta, Silvia, Meucci, Lorenza, Giacosa, Donatella, Marino, Elena, Gorrasi, Ilaria, Gilli, Giorgio, Carraro, Elisabetta
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Disinfection of hot water systems is critical for reducing Legionnaires’ disease in high-risk buildings. The use of neutral electrolysed oxidising water (NEOW) is a promising method for the control of microorganisms in hot water systems. However, full-scale evaluations of the efficacy of NEOW devices to control Legionella pneumophila are currently lacking. The aim of this study was to assess the effectiveness of a NEOW device in reducing L. pneumophila in a hotel water network. Water samples (n = 67) were collected from different sites of a hotel distribution system before and after the installation of the NEOW device at the 1st, 4th, 8th and 12th week. Detection of L. pneumophila was performed comparing culture, qPCR and PMA-qPCR methods. Total bacterial counts (22 °C and 37 °C), Pseudomonas spp. and physico-chemical parameters were also monitored. The NEOW treatment resulted in a reduction of the amount of L. pneumophila positive samples (−32%) and of the number of heavily contaminated points (>104 CFU/L and >103 CFU/L) (−100% and −96%, respectively). Treatment maintained L. pneumophila at low levels (