Evaluation of Ceramic and Membrane Diffusers under Operating Conditions with the Dynamic Offgas Method
The aeration systems of two full-scale, activated-sludge basins were compared during a period of three years, under the same operating conditions, using dynamic offgas testing. Only the material of the diffuser was different (membrane versus ceramic-tube diffusers). The investigation has shown that,...
Gespeichert in:
Veröffentlicht in: | Water environment research 2005-09, Vol.77 (5), p.447-454 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The aeration systems of two full-scale, activated-sludge basins were compared during a period of three years, under the same operating conditions, using dynamic offgas testing. Only the material of the diffuser was different (membrane versus ceramic-tube diffusers). The investigation has shown that, although the membrane diffusers have higher initial standard-oxygen-transfer efficiency (αSOTE) and standard-aeration efficiency (αSAE), these decreased over time, while the αSAE of the ceramic diffusers started lower, but increased slightly over the whole period. A cost comparison makes clear how important it is to evaluate the aeration system under process conditions. The operating costs were the dominant factor (∼10× higher than capital costs), and operating costs were approximately 20% higher for membrane versus ceramic diffusers. The poor performance of the membrane-tube diffusers under process conditions could be explained on the basis of the actual αAE values in the basin, not the standardized values. |
---|---|
ISSN: | 1061-4303 1554-7531 |
DOI: | 10.2175/106143005X67359 |