Wastewater pond systems using chemical precipitation (fellings dams): state of the art in Sweden
Chemical precipitation in wastewater stabilization ponds - in Scandinavia called fellings dams - has been in operation for more than 50 years. Slaked lime and aluminium salts are the most common chemicals used for precipitation. Long and narrow forms of the ponds and a detention time of at least 5 d...
Gespeichert in:
Veröffentlicht in: | Water science and technology 2017-11, Vol.76 (9-10), p.2623-2629 |
---|---|
Hauptverfasser: | , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Chemical precipitation in wastewater stabilization ponds - in Scandinavia called fellings dams - has been in operation for more than 50 years. Slaked lime and aluminium salts are the most common chemicals used for precipitation. Long and narrow forms of the ponds and a detention time of at least 5 days have shown, even at a low water temperature and below an ice cover, to produce an average effluent quality of 70 mg COD
/l, 0.2 mg Tot-P/l, 20 mg Tot-N/l (CODCr: chemical oxygen demand; Tot-P: total phosphorus; Tot-N: total nitrogen) and low levels of pathogenic bacteria. The systems use low amounts of energy and no wastewater is by-passed at the plants. Fellings dams have recently been tried to support overloaded wastewater collection systems. |
---|---|