Derivation of zero-sequence circulating current and the compensation of delta-connected static var generators for unbalanced load

Cascaded static var generators (SVG) with delta-configuration is discussed for a compensation of reactive, negative-sequence and harmonic currents. According to phasor analysis of negative-sequence current compensation, the role of zero-sequence circulating current for power balance is analysed. Acc...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IET power electronics 2016-03, Vol.9 (3), p.576-588
Hauptverfasser: Fujun, Ma, An, Luo, Qiaopo, Xiong, Zhixing, He, Qianming, Xu
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Cascaded static var generators (SVG) with delta-configuration is discussed for a compensation of reactive, negative-sequence and harmonic currents. According to phasor analysis of negative-sequence current compensation, the role of zero-sequence circulating current for power balance is analysed. According to power analysis, the analytical expressions of zero-sequence circulating current and 2nd frequency ripples of dc-link voltages are derived. On the basis of this, the phase-current reference detection and the simplified control method of SVG for negative-sequence current compensation are proposed, which is concise and can achieve power balance of three-phase clusters by superimposing a zero-sequence circulating current without additional controllers. Finally, the simulation and experimental results have effectively verified the proposed method.
ISSN:1755-4535
1755-4543
1755-4543
DOI:10.1049/iet-pel.2014.0682