Procedure for assessing hardware safety integrity in legacy systems
Functional safety is related to the safety functions of a safety-related system that uses electrical/electronic/programmable (E/E/PE) devices such as sensors, logic solvers, and final elements. A legacy system is a safety-related system which offers safety functions but which was not designed to com...
Gespeichert in:
Veröffentlicht in: | Journal of loss prevention in the process industries 2016-03, Vol.40, p.461-470 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Functional safety is related to the safety functions of a safety-related system that uses electrical/electronic/programmable (E/E/PE) devices such as sensors, logic solvers, and final elements. A legacy system is a safety-related system which offers safety functions but which was not designed to comply with the IEC 61508 standard. This paper presents a procedure for assessing the hardware safety integrity of a legacy system so as to confirm its functional safety. The procedure defines the systematic relationship between the safety function and hardware system using a function-structure map (FSM) and assesses the hardware safety integrity centered on the safety function. The proposed procedure is applied to a boiler control system of a fossil-fuel power plant.
•This research presents a procedure for assessing the hardware safety integrity of a legacy system.•A function-structure map is used to respond effectively to the safety functions of the related hardware components and to prevent an error that an SIL evaluation is performed for safety-related systems.•The proposed assessment procedure is applied to a boiler control system of a fossil-fuel power plant.•The hardware SIL of each safety function is determined to be SIL3 in the boiler control system. |
---|---|
ISSN: | 0950-4230 1873-3352 |
DOI: | 10.1016/j.jlp.2016.01.019 |