Evaluation of High-Rate Clarification for Wet-Weather-Only Treatment Facilities

High-rate clarification (HRC) processes are well suited for enhanced primary treatment of wet-weather flows in combined sewer systems. Suspended solids removal in excess of 75% of influent concentrations can be achieved consistently. Chemical oxygen demand and five-day biochemical oxygen demand remo...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Water environment research 2004-09, Vol.76 (5), p.474-480
Hauptverfasser: Jolis, Domènec, Ahmad, Meei-Lih
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:High-rate clarification (HRC) processes are well suited for enhanced primary treatment of wet-weather flows in combined sewer systems. Suspended solids removal in excess of 75% of influent concentrations can be achieved consistently. Chemical oxygen demand and five-day biochemical oxygen demand removal are better than 60%. However, although optimal treatment could be achieved in a matter of minutes when the units were started full, a delay of up to one-half hour was observed when the units were started empty. Operational strategies that minimize this effect need to be developed in full-scale tests before HRC processes can be implemented with confidence in wet-weather-only facilities.
ISSN:1061-4303
1554-7531
DOI:10.2175/106143004X151563