A new on-line monitoring method of transformer winding axial displacement based on measurement of scattering parameters and decision tree
► Transformer winding axial displacement can be detected by comparison of S-parameters. ► The measured S-parameters are compared with the latest measurements (time-based). ► Two indices ( MAMD and MAPD) are defined from the magnitude and phase of S-parameters. ► The decision tree method has a good a...
Gespeichert in:
Veröffentlicht in: | Expert systems with applications 2011-07, Vol.38 (7), p.8886-8893 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | ► Transformer winding axial displacement can be detected by comparison of
S-parameters. ► The measured
S-parameters are compared with the latest measurements (time-based). ► Two indices (
MAMD and
MAPD) are defined from the magnitude and phase of
S-parameters. ► The decision tree method has a good accuracy to determine the winding displacement.
In this paper the scattering parameter of a simplified model of transformer has been measured in different axial displacement of the winding using a Network Analyzer. Two indices have been suggested to detect the axial displacement. The measurement results show the effectiveness of these indices. A new method of the detection of the axial displacement extent based on decision tree (DT) has been proposed, too. It has been shown that this method has a good accuracy to determine the displacement of the winding and its extent. |
---|---|
ISSN: | 0957-4174 1873-6793 |
DOI: | 10.1016/j.eswa.2011.01.100 |